Standard: | IEC/EN61009 | Rated Current: | 6-63A |
---|---|---|---|
Pole Number: | 2P , 4P | Rated Voltage: | 230V/415V |
Tripping Curve: | C,B,D Curve | Function: | Leakage Protection |
Residual Current: | 10mA,30mA,100mA | Mounting: | Din-rail Type |
Mechanical Life: | 10000 Times | Application: | Household,Terminal Distribution,Electrical Power,widely,Electricity Distribution Room |
High Light: | EN61009 RCBO Breaker,EN61009 rc circuit breaker,Type C RCBO Breaker |
IEC/EN61009 Standard Hager 32 Amp Rcbo Type C With Overload Protection
General description
1.Protection against overload and short-circuit currents
2.Protection against the effects of sinusoidal alternating earth fault currents
3.Protection against indirect contacts and additional protection against direct contacts.
4.Protection against fire hazard caused by insulation faults
5.Used in residential building
6.According to the type of instantaneous release classified as follows : type B(3-5)ln,type C(5-10)ln,type D(10-20)In
Main Technical Parameter
Poles | 1P+N 2 3 3P+N 4 |
Electrical Life (t) | 2000 |
Rated Voltage Ue (V) | 230/400 |
Insulation Voltage Ui (V) | 500 |
Rated frequency (Hz) | 50/60 |
Rated shor-circuit capacity (Icn) | 4500 |
Terminal connection type | Cable / Pin-type busbar |
Connection | From top |
Rated Current In (A) | 6, 10, 16, 20, 25, 32, 40, 50, 63 |
Product Keywords | 40a elcb rcbo,400v rcbo circuit breaker,400v 4 pole rcbo |
The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
Cold position | 1.13In | t ge 1h | Non-release | - | |
30plusmn2oC | Carried out immediately after previous test | 1.45In | t<1h | Release | - |
Cold position | 2.55In | 1s < t < 60s | Release | Current smoothly rises to specified value within 5s | |
-5~+40oC | Cold position | 5In | t ge 0.1s | Non-release | Type C |
Cold position | 10In | t < 0.1s | Release | Type C |
IEC/EN61009 Standard Hager 32 Amp Rcbo Type C With Overload Protection
IEC/EN61009 Standard Hager 32 Amp Rcbo Type C With Overload Protection